Section 26 41 13 (Formerly
16670) – L IGHTNING PROTECTION SYSTEM SPECIFICATION
GENERAL
1.01 Summary:
a. Provide a complete lightning protection system for the
building(s) or structures included on the contract drawings.
The system shall provide safety for the building, the buildings
contents and occupants by preventing damage caused by lightning.
The design of this system is to be in strict accordance
with this section of the specifications and all contract
drawings that apply.
b. The lightning protection system shall be installed by
a firm actively engaged in the installation of Master Labeled
Lightning Protection Systems and shall be so listed by Underwriters
Laboratories Inc. The completed system shall comply with
the latest editions of the Installation Requirements for
Lightning Protection Systems, UL96A and of the National
Fire Protection Association’s Lightning Protection
Standard, NFPA 780.
c. The work covered under this section of the specification
consists of furnishing labor, materials and services required
for the completion of a functional and unobtrusive lightning
protection system approved by the architect, engineer and
Underwriters Laboratories Inc.
1.02 References:
The completed lightning protection system shall comply with
the latest issue of the following standards and form a part
of this specification.
a. NFPA 780, Standard for the Installation of Lightning
Protection Systems.
b. UL 96A, Installation Requirements for Lightning Protection
Systems
1.03 Submittals:
a. Shop drawings shall be submitted to the architect and
engineer for approval prior to commencement of the installation.
Shop drawing are to show the extent of the system layout
designed specifically for the building(s) or structures
included in the contract drawings along with details of
the products to be used in the installation.
1.04 Quality Assurance:
a. The installing contractor shall furnish a UL Master Label
upon completion of the installation.
PRODUCTS
2.01 Standard:
a. All materials used in the installation shall be new and
shall comply in weight, size and composition as required
by UL 96A and NFPA 780 and shall be labeled or listed by
Underwriters Laboratories Inc. for use in lightning protection
systems. The system furnished under this specification shall
be the standard product of a manufacturer regularly engaged
in the production of lightning protection equipment. The
manufacturer shall be listed by UL as a recognized manufacturer
of lightning protection components.
2.02 Acceptable Manufacturers:
a. Harger Lightning & Grounding
301 Ziegler Drive, Grayslake, IL 60030
(847) 548-8700 800-842-7437 Fax (847) 548-8755
E-mail: hargersales@harger.com Web-site: www.harger.com
b. Dillon Lightning Protection Systems, Inc
4702 Fishers Hollow Road
Myersville, Maryland 21773
301-696-9027
301-696-9029 fax
E-mail: dillonlp@aol.com
Contact: Matthew P. Dillon (LPI Master Installer/Designer
# 1038)
2.03 Materials:
a. Class I materials shall be used on structures that do
not exceed 75 feet in height and Class II materials shall
be used on structures that are 75 feet or higher above average
grade.
b. Copper materials shall not be mounted on aluminum surfaces
including Galvalume, galvanized steel and zinc; this includes
these materials that have been painted.
c. Aluminum materials shall not come into contact with earth
or where rapid deterioration is possible. Aluminum materials
shall not come into contact with copper surfaces.
2.04 Air Terminals:
a. Air terminals shall project a minimum of ten inches above
the object or area it is to protect and shall be located
at intervals not exceeding 20’-0” along ridges
and along the perimeter of flat or gently sloping roofs
(flat or gently sloping roofs include roofs that have a
pitch less than 3:12). Flat or gently sloping roofs exceeding
50’-0” in width shall be protected with additional
air terminals located at intervals not exceeding 50’.
Air terminals shall be located within two feet of roof edges
and outside corners of protected areas.
b. Air terminals shall be installed on stacks, flues, mechanical
units and other metallic objects not located within a zone
of protection and which have an exposed metal thickness
less than 3/16 of an inch. Objects having an exposed metal
thickness 3/16 of an inch or greater shall be connected
to the lightning protection system as required by the specified
standards using main size conductor and bonding plates having
a minimum of 3 square inches of surface contact area.
c. Air terminal bases shall be securely fastened to the
structure in accordance the specified standards including
the use of adhesive that is compatible with the surface
it is to be used on or stainless steel fasteners.
d. Main conductors shall be sized in accordance with the
specified standards for Class I or Class II structures and
shall provide a two way horizontal or downward path from
each air terminal to connections with the ground system.
Conductors shall be free of excessive splices and no bend
of a conductor shall form a final included angle of less
than neither 90 degrees nor have a radius of bend less than
8 inches.
e. Down conductors shall
be sized in accordance with the specified standards and
in no case shall be smaller than the main roof conductor.
Down conductors shall be spaced at intervals averaging not
more than 100 feet around the perimeter of the structure.
In no case shall a structure have fewer than two down conductors.
Where down conductors are installed exposed on the exterior
of a structure and are subject to physical damage or displacement,
guards shall be used to protect the conductor a minimum
of 6 feet above grade. Metallic guards shall be bonded at
each end.
f. In case of structural steel frame construction, down
conductors may be omitted and roof conductors shall be connected
to the structural steel frame at intervals not exceeding
100 feet along the perimeter of the structure.
2.05 Roof Penetrations:
a. Roof penetrations required for down conductors or for
connection to structural steel framework shall be made using
thru-roof assemblies with solid riser bars and appropriate
roof flashing. Conductors shall not pass directly through
the roof. The roofing contractor shall furnish and install
the materials required to properly seal all roof penetrations
of the lightning protection components and any additional
roofing materials or preparations required by the roofing
manufacturer for lightning conductor runs to assure compatibility
with the warranty for the roof including roof pads that
may be required to protect the roof under each of the lightning
protection components.
2.06 Ground Terminations:
a. Ground electrodes shall be copper clad steel and a minimum
5/8” diameter and 10 feet long. A ground electrode
shall be provided for each down conductor. The down conductor
shall be connected to the ground electrode using a bronze
ground rod clamp having a minimum of 1 ½” contact
between the ground electrode and the conductor measured
parallel to the axis of the ground electrode, or by an Ultraweld
exothermically welded connection. Ground electrodes shall
be located a minimum of 2 feet below grade and shall be
installed below the frost line where possible (excluding
shallow topsoil conditions).
b. Where the structural steel framework is utilized as the
down conductor for the system, ground terminals shall be
connected to columns around the perimeter of the structure
at intervals averaging not more than 60 feet apart. Columns
shall be grounded using either bonding plates having 8 square
inches of surface contact area or by Ultraweld exothermically
welded connections.
c. All ground electrodes shall be interconnected with a
ground loop conductor on structures that exceed 60 feet
in height. The ground loop conductor shall be sized in accordance
with the specified standards and in no case shall be smaller
than the main roof conductor.
2.07 Equipotential Grounding:
a. Common interconnection of all grounded systems within
the building shall be ensured by interconnecting to the
lightning protection system using main size conductor and
fittings.
b. This interconnection shall include but is not limited
to the electrical service, telephone and antenna system
grounds as well as all underground metallic piping systems
including water, gas and sewer. Interconnection to a gas
or water line shall be made on the customer’s side
of the meter.
c. Grounded metal bodies located within the required bonding
distance as determined by the bonding distance formula in
the latest edition of NFPA-780 Standard for the Installation
of Lightning Protection Systems shall be bonded to the lightning
protection system using the required bonding conductors
and connections.
2.08 Surge Protection:
a. Surge suppression shall be provided at all power service
entrances and at entrances of conductive signal, data and
communication services.
Part 3 – EXECUTION
3.01
Installation:
a. The installation shall be installed by an UL listed lightning
protection installation company.
3.02 Coordination:
a. Coordinate the installation of the lightning protection
system with other trades
b. Coordinate all roof penetrations, fasteners and adhesive
with the roofing contractor prior to installing any materials
on the roof.
3.03 Inspection and Certification:
a. New Structures:
i Upon completion of the installation of the lightning protection
system the contractor shall furnish the UL Master Label
issued by Underwriters Laboratories Inc.
b. Additions or renovations:
i If the protected structure is an addition to or is attached
to an existing structure that does not have a functioning
lightning protection system, the contractor shall certify
that the new system installed complies with the specified
standards and shall advise the owner on the lightning protection
work required on the existing structure so that a Master
Label may be obtained.
ii If the protected structure is an addition to or is attached
to an existing structure that does have a lightning protection
system the contractor shall advise the owner of any additional
work that may be required in order to bring the existing
lightning protection system into compliance with the specified
standards and thus qualify for a Reconditioned Master Label
from Underwriters Laboratories Inc.